BS 7671 Part 4: Protection for Safety, Explained

Part 4 in the order the paper asks it: disconnection times, Zs against Table 41.3, TT systems, 30 mA RCDs and the two overcurrent checks.

What Part 4 actually decides

Part 4 answers one question per circuit: if something goes wrong, does the protective device clear the fault fast enough that nobody is still touching the metal when it does? Everything else in the part is the arithmetic behind that sentence.

It runs in four chapters. Chapter 41 is protection against electric shock, 42 is thermal effects, 43 is overcurrent, 44 is voltage disturbance and electromagnetic compatibility. The paper spends almost all its Part 4 questions on chapter 41 and the disconnection times.

Chapter 41: the disconnection times

System Final circuit not over 32 A Distribution circuit
TN (TN-S, TN-C-S) 0.4 s 5 s
TT 0.2 s 1 s

Those are the numbers from Table 41.1 and they are the first thing to know cold. Note what the 0.4 s is attached to: a final circuit up to 32 A. A 40 A shower circuit is not in that row, and a question that gives you a 40 A circuit and a 0.4 s answer is testing whether you noticed.

Chapter 41: Zs, and why the table matters more than the meter

For a TN system, the device clears the fault only if the earth fault loop impedance is low enough for enough current to flow. You do not calculate that under exam pressure — you look up the maximum in Table 41.3 and compare.

Two values worth carrying in your head for 230 V TN circuits: a 32 A Type B MCB is 1.37 ohm, a 6 A Type B is 7.28 ohm. Measure above the tabulated maximum and the circuit does not comply, whatever the tester says about continuity.

Three things follow from that, and they come up in the exam as three different questions:

Chapter 41: TT systems and RCDs

A TT installation has no metallic path back to the supply transformer, so the fault loop goes through the mass of earth and the impedance is far too high to blow a fuse. Fault protection therefore depends on an RCD. That is Regulation 411.5, and it is the reason a TT board with no RCD is not a compliant board.

Separately, Regulation 411.3.3 requires additional protection by a 30 mA RCD for socket-outlets rated up to 20 A for general use, and for circuits of mobile equipment used outdoors. Additional is the word to hold on to: it sits on top of the basic protection, it does not replace it.

Chapter 43: overcurrent

Two ideas, one inequality each.

Ib ≤ In ≤ Iz — design current no greater than the device rating, device rating no greater than the cable's current-carrying capacity. Get the order wrong and you have either a cable that overheats or nuisance tripping.

Fault current withstand — the protective conductor and the cable's sheath have to survive the energy let through until the device operates, which is what the k²S² check is for. The paper rarely asks you to run the sum; it does ask you to recognise which of the two checks a scenario is about.

Where Part 4 meets the other parts

Part 4 says what the circuit must achieve. Part 5 says how to build it so it does — cable sizing, the 50 mm rule for concealed cables, voltage drop in Appendix 4 at 3 per cent for lighting and 5 per cent for everything else in a private installation. Part 6 then proves it with a measurement. When a question asks why a circuit fails, the answer is often in Part 4, and fixing it is often in Part 5.

The four traps in this part

  1. Confusing basic protection (insulation, barriers, enclosure) with fault protection (earthing and disconnection) and additional protection (30 mA RCD).
  2. Applying the 0.4 s row to a circuit over 32 A.
  3. Treating a TT system as if the supply fuse will clear an earth fault.
  4. Forgetting that a 30 mA RCD does not excuse a high Zs on a TN circuit — you still have to meet the disconnection time by one means or another, and the RCD route is a different regulation.

Is Part 4 the biggest part of the exam?

It carries a lot of the marks, but not because it is long — because the numbers are checkable. If you can quote the disconnection times and the Zs method without opening the book, you have bought yourself time for the parts that need the index.

Do I need to memorise any tables?

Three quarters of the paper is designed to be answered with BS 7671 open in front of you. Memorise the shape of the tables and the handful of numbers you use weekly; look up the rest, quickly.

How does this connect to the AM2?

Section B is Part 6 in practice. The Zs and RCD results you record there are only compliant if they satisfy Part 4 — which is why the drills make you compare a reading to Table 41.3 rather than just read a meter.