The 50 mm rule, accessible connections, bonding sizes, cable derating and the 3 and 5 per cent voltage drops — Part 5 as it is actually asked.

What Part 5 covers

Part 5 is the longest part of BS 7671 and the one the paper asks about least directly, which makes it easy to under-revise and then lose marks to it. It runs from chapter 51 (common rules) through 52 (selection and erection of wiring systems), 53 (isolation, switching and control), 54 (earthing and bonding), 55 (other equipment) to chapter 56 (safety services).

In practice it answers one question: having decided what the circuit must achieve in Part 4, how do you build it so that it does?

The 50 mm rule, and why it is the most-asked clause

A cable concealed in a wall or partition at a depth of less than 50 mm, without earthed metallic covering, must have additional protection by a 30 mA RCD unless it is in a recognised safe zone or protected by an earthed metallic barrier. Regulation 522.6.6.

Everything you need to answer questions on it is in that sentence: the depth, the exception for earthed metallic covering, the safe zones, and the word additional. The exam likes it because it is a real job and because the wrong answers all look like something an electrician has actually said on site.

Connections

Every connection must be accessible for inspection, testing and maintenance (Regulation 526.3). That is why a joint in a ceiling void that will be boarded over is a problem even when it is a good joint — the regulation is about access, not about workmanship, and the exam will always offer you “made properly with a good connector” as a wrong option.

Bonding sizes

Table 54.8 sizes the main protective bonding conductor from the supply type and the neutral. The number to keep available is 10 mm² for a TN-C-S (PME) supply, and the principle is that bonding is sized from the supply, not from the pipe it is clamped to. Supplementary bonding in a bathroom is 4 mm² when it is not mechanically protected, and is often unnecessary if the disconnection times are met by RCD.

Cable capacity is not a table lookup

Iz is the tabulated capacity in Appendix 4 corrected by every factor that applies: ambient temperature (Ca), grouping (Cg), thermal insulation (Ci), and the method of installation. The exam gives you the factors and asks you to combine them; real work requires the same discipline. The two most common real-world mistakes are a cable under loft insulation with no derating and a cable bunched with six others with no grouping factor.

Voltage drop, and where it lives

Appendix 4, not Part 5 — but it is Part 5's job to satisfy it. 3 per cent for lighting, 5 per cent for other uses in a private installation, measured from the origin. A circuit that passes Zs and still gives the customer flickering lights has usually failed this.

Selection, not just installation

The chapter 52 material on external influences is worth ten minutes: IP ratings for wet and dusty locations, impact and corrosion, and equipment suitable for the environment rather than convenient for the installer. If a question describes a farm building, a car wash or a basement, the answer is usually about the environment, not the cable.

How this connects to the other parts

Part 3 tells you the conditions, Part 4 gives the limits, Part 5 is the build, and Part 6 proves it. When you get a Part 5 question wrong, the fix is usually to ask which of those four the question is really about — a surprising number of them are Part 6 questions asked with a Part 5 example.

Is the 50 mm rule about depth from the surface?

Yes — from the finished surface of the wall or partition to the cable, and the mention of earthed metallic covering is the exception that lets the RCD be omitted.

Can I use a junction box in a loft?

Yes if it remains accessible for inspection and testing. Under a boarded floor with no access, no.

Does bonding have to be 10 mm² every time?

No. It is sized from Table 54.8 by supply type and neutral, and 10 mm² is the number that applies to the common PME domestic case.