BS 7671 Part 7: Special Installations and Locations

Part 7 as a set of locations rather than a list: bathroom zones, 110 V on site, DC in a PV array and what an EV charge point needs.

What Part 7 does differently

Parts 1 to 6 apply everywhere. Part 7 applies in addition, to locations where the conditions make the ordinary rules insufficient — wet, restricted, skilled-only, or where the consequences of a fault are worse than usual. Each section is numbered, and the numbers are what the paper uses to test you.

Section Location
701 Locations containing a bath or shower
702 Swimming pools and fountains
704 Construction and demolition sites
705 Agricultural and horticultural premises
708 Caravan and camping parks
709 Marinas and similar locations
710 Medical locations
711 Exhibitions, shows and stands
712 Solar photovoltaic systems
715 Extra-low voltage lighting installations
717 Mobile or transportable units
721 Caravans and motor caravans
722 Electric vehicle charging installations

You do not need to memorise all of it. You do need to recognise which section a scenario belongs to, because that decides the answer to every other question about it.

701: the bathroom, in three zones

Zone 0 is the inside of the bath or shower basin itself. Zone 1 is the space above it, up to 2.25 m from the floor. Zone 2 is the 0.6 m band around zone 1. The old zone 3 was removed: the 2.25 m line does its job now.

What follows: equipment must be suitable for the zone, socket-outlets are not permitted in zones 0, 1 and 2, and supplementary bonding can be omitted where the disconnection times are met by 30 mA RCD protection and the requirements for extraneous conductive parts are satisfied. That last point is the one most candidates miss, because it was drilled into them for years that bathroom bonding is compulsory.

704: construction sites

Reduced low voltage is the convention — 110 V centre-tapped to earth, so 55 V to earth — and every socket and plug is of a type that cannot be connected to the 230 V system. RCD protection is required, and the whole assembly is built for rough handling. The exam often words this as a question about why 110 V is safer: the answer is the centre tap, not the lower number on its own.

722: EV charging, the section that keeps changing

An EV charge point needs protection against DC residual current, either built into the device or provided by a Type B RCD, plus the usual 30 mA additional protection. The cable and the point are outside the equipotential zone, which is exactly the condition that TN-C-S bonding guidance is uneasy about — so the installation method (and often an earth electrode) matters.

712: solar PV

The DC side is a live part even when the AC isolator is off, and it is a live part in daylight. Isolation for work on the installation therefore needs a DC isolator, and the array is not “dead” just because the inverter has shut down. If a question has a PV array and an isolator in it, check whether it is asking about the array generating or the inverter converting.

How the paper asks Part 7

Almost always as a location plus a decision: what may be installed here, what protection does this need, who may work on it. The order of thinking that scores points is: name the section, name the extra requirement, then apply Part 4 as usual. The mistake that costs marks is answering from Part 4 alone and forgetting the location ever existed.

Is bathroom supplementary bonding still required?

Not always. It can be omitted where the disconnection times are achieved by 30 mA RCD protection and the conditions for extraneous conductive parts are met — check the current wording of section 701 rather than the habit you were taught.

Which section covers a garden office with a hot tub?

Outdoors plus water: 702 for the pool or hot tub itself, and the general rules for everything else. The location decides, not the address.

Do special locations affect the AM2?

They affect the design decisions you make on the rig and the questions the assessor asks about them, and they are worth marks in section E. The written practice includes Part 7 questions for that reason.